Batiboard T
reaction to fire A1
Uncombustible mineral board including high temperature fibres. Product with a classification temperature of 1400°C. Alternative to spraying solutions. Has lower thickness and handling weight than traditionally-used competitor boards. Performs 2 hours in 20mm and 3hours in 30 mm when protecting concrete and tested under RWS elevation of temperature. Under EU European Technical Assessment.
Characteristics
Batiboard reference | Batiboard T | Unit | Test method |
---|---|---|---|
Nominal density | 500 | kg/m3 | EN 1602 |
Thickness range | 9 - 30 | mm | EN 823 |
Standard dimensions (mm) | 1200x1000 and 2400x1200 | mm | EN 822 |
Reaction to fire (Euroclass) | A1 | EN 13501-1 | |
Classification Temperature | 1400 | °C | internal |
Thermal conductivity at 100/ 200/ 400/ 600/ 800/1000/1200 and 1400°C | 0.06/ 0.07/ 0.09/ 0.11/ 0.14/ 0.18/ 0.24 / 0.32 | W/m.K | ASTM C201 |
Tensile strength, perpendicular plane of board, internal bond | 130 | kPa | EN 319 |
Compression strength, in plane | 1610 | kPa | EN 789 § 8 |
Tensile strength | 1100 | kPa | EN 789 § 9 |
Dimensions monolithic plates
STANDARD THICKNESSES (MM) | 10 | 15 | 20 | 25 | 30 |
---|---|---|---|---|---|
Number of boards per pallet | 102 | 72 | 54 | 42 | 36 |
Standard dimensions (mm) | 2100 x 900 and 2400 x 1200 | ||||
Maximum dimensions (mm) | 2400 x 1200 | 3000 x 1200 | |||
Length and width tolerance (mm) | +/- 1 up to 1200 and +/- 2 above | ||||
Standard thickness tolerance (mm) | +/- 1 | +/- 2 | |||
Ground plates Thickness tolerance (mm) | (-0.5/+0.5) or (-1/+0) or (-0/+1) | ||||
Flatness (mm/m) | +/- 2 |